The contact closure module will be preset to use the following IP address:
Port X001 (maintenance) - 192.168.0.11
Port X101/X102 (data) - 192.168.127.254
NOTE: The IP address can be changed based on the needs of your network. You must have an active network connection to port X101.
1. Verify the DIP switch matches the following settings:
- Switches 1-8 are in the ON position while switches 9 and 10 are in the OFF position.
2. Set the IP address of your PC to 192.168.0.99
3. Connect the network cable from your PC to the maintenance port X001.
4. Open an Internet Browser and navigate to the following URL: https://192.168.0.11/config/
5. Enter login credentials:
- Username: administrator
- Password: Echo123
6. In the Hardware section, click NIC.
7. Set "TCCATMP1" address and default gateway to desired subnet.
8. Click the check mark button after the network changes have been made to TCCATMP1.
9. In the Device section, click Boot.
10. Click the Reboot button at the bottom of the screen to reboot the system.
11. Verify the IP address after the reboot.
12. Connect the Echo Ethernet port and CX8190 X101 Ethernet port to network switch or point to point.